EN 50575 Explained: EU CPR Cable Fire Standard & Euroclasses
Quick answer: EN 50575:2014+A1:2016 is the harmonised European standard that puts power, control and communication cables under the Construction Products Regulation (EU) 305/2011. It classifies a cable's reaction to fire into seven Euroclasses — Aca, B1ca, B2ca, Cca, Dca, Eca, Fca — with extra s (smoke), d (droplets) and a (acidity) sub-classes. It has been mandatory since 1 July 2017, applies to cables permanently installed in buildings, and requires a Declaration of Performance (DoP) and CE marking. It covers reaction to fire only — not fire resistance.

What EN 50575 Actually Is
If a cable is permanently installed in a European building — power, control, communication or fibre — it must carry a CE marking under the Construction Products Regulation (CPR, Regulation (EU) No 305/2011). EN 50575 is the harmonised standard that defines how that cable's fire performance is tested, classified, verified and declared. The fire classes themselves are defined in EN 13501-6.
Two things are frequently confused, so state them plainly:
Reaction to fire (EN 50575's scope): how much a cable contributes to a fire that has already started elsewhere — flame spread, heat release, smoke, droplets, acidity.
Fire resistance (out of scope): how long a cable keeps circuit integrity during a fire, e.g. 30/60/90 minutes for life-safety systems. That is a separate requirement.
The standard has been mandatory across the EU since 1 July 2017 (UK: BS EN 50575:2014+A1:2016, UKCA/CE). Equipment-internal wiring, mobile cords, automotive, marine and temporary-installation cables generally fall outside CPR scope.
The Seven Euroclasses (Aca to Fca)
The "ca" suffix stands for cable. Classes run from best to worst; lower heat release and flame spread mean a better class.
Class | Performance | Main test | AVCP system |
|---|---|---|---|
Aca | Non-combustible, highest class | EN ISO 1716 | 1+ |
B1ca / B2ca | Very limited fire contribution | EN 50399 + EN 60332-1-2 | 1+ |
Cca | Limited fire contribution | EN 50399 (20.5 kW) + EN 60332-1-2 | 1+ |
Dca | Medium contribution, general building work | EN 50399 + EN 60332-1-2 | 3 |
Eca | Minimum compliant — single cable does not propagate flame | EN 60332-1-2 | 3 |
Fca | Does not meet Eca — no performance declared | EN 60332-1-2 | 4 |
Key point for buyers: Eca is the floor, not a premium. It is the minimum class that satisfies CPR for general building cable. Fca cable has no declared fire performance and must not be used where CPR applies.
Reading the Full Class Code: s, d and a
For classes B1ca to Dca, three additional characteristics are declared, written as a suffix such as Cca-s1a,d0,a1:
s — smoke production (s1, s1a, s1b, s2, s3): s1a is best (≥80% light transmittance). Low smoke protects evacuation visibility.
d — flaming droplets (d0, d1, d2): d0 = no droplets; d1 = none lasting >10 s; d2 = not regulated. Droplets can ignite secondary fires.
a — acidity (a1, a2, a3): a1 is least acidic/corrosive, protecting equipment and circuits during a fire.
Lower numbers are better: Cca-s1a,d0,a1 outperforms Cca-s1b,d2,a2. Note that s/d/a sub-classes apply only to B1ca–Dca; Eca is declared without them.
AVCP: Who Certifies What
The Assessment and Verification of Constancy of Performance route depends on the class — this determines whether a notified body is involved:
System 1+ (Aca–Cca): a notified product-certification body type-tests, audits the factory production control, and performs ongoing surveillance and audit testing. Cca and above cannot be self-declared.
System 3 (Dca, Eca): a notified testing laboratory type-tests; the manufacturer runs its own factory production control.
System 4 (Fca): no third-party involvement, manufacturer self-declaration.
CPR harmonises the technical language; it does not set the minimum class for a given installation. National rules and project specifications (e.g. BS 6701 in the UK) decide which Euroclass a project actually requires — always match the class to the building's fire strategy.
EN 50575 vs Solar Cable Standards — Don't Conflate Them
A frequent sourcing error is treating a CPR building-wire rating as a photovoltaic cable rating, or vice versa. They answer different questions:
EN 50575 / CPR — fire reaction of permanently installed building wiring (Euroclass Eca, Cca-s1a,d0,a1, etc.).
EN 50618 / IEC 62930 — 1500 V DC solar cable, specifying UV/weather resistance, XLPO insulation, temperature range.
CB scheme / IEC 60898-style product certification — a separate route for market access, see our certification map.
A PV installation that runs cable inside a building may need both a solar-cable rating for the DC side and an appropriate CPR Euroclass for the fixed wiring — check the project's fire strategy rather than assuming one certificate covers all.
Frequently Asked Questions
Q: Is EN 50575 mandatory in the EU?
A: Yes. It has applied to power, control and communication cables permanently installed in buildings since 1 July 2017 under CPR (EU) 305/2011. The UK equivalent is BS EN 50575:2014+A1:2016.
Q: What is the difference between Eca and Cca cable?
A: Eca is the minimum compliant class — a single cable does not propagate flame (EN 60332-1-2). Cca is a higher class tested for limited heat release and flame spread (EN 50399) with smoke/droplet/acidity sub-classes, and requires notified-body certification (System 1+).
Q: What does Cca-s1a,d0,a1 mean?
A: A CPR Euroclass code: Cca fire class, s1a low smoke (≥80% light transmittance), d0 no flaming droplets, a1 least acidic smoke. Lower numbers are better. These sub-classes apply to B1ca–Dca.
Q: Does EN 50575 cover fire resistance?
A: No. It covers reaction to fire only. Fire resistance — maintaining circuit integrity for 30–120 minutes — is a separate requirement and is explicitly outside CPR's scope.
Q: What document must a supplier provide for CPR cable?
A: A Declaration of Performance (DoP) stating the Euroclass, the standard (EN 50575) and — for Aca–Eca — the notified body involved, plus CE marking on the cable, drum or box. Verify the class matches the project specification.
About the guide
Written by Engineer Chan for SolaCable — a supplier of certified solar cables, MC4 connectors and IP68 cable glands. This guide summarises public EN 50575:2014+A1:2016 / CPR (EU) 305/2011 requirements; always confirm the exact class required by the project and the current national rules before procurement. See our certification map →